Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013 89
Using the I/O Chapter 5
Figure 17 - ControlLogix Controller Example Ladder Logic Program Using a Drive Generic Profile
for Logic Command/Reference
Example Datalink Data
The Datalink data used in the example program is shown in Figure 18. Note that
to describe the parameters to which the Datalinks are assigned, you may want to
add descriptions to the automatically-created generic controller tags or create a
UDDT. For this example, the DL_From_Net tags were created to describe the
drive parameters to which these Datalinks are assigned. For example,
DL_From_Net_01_Stop_Mode_A indicates that adapter Parameter 01 - [DL
From Net 01] is assigned to drive parameter 370 - [Stop Mode A]. This same
method applies to the DL_To_Net tags.