Specifications
This appendix presents the specifications for the adapter.
Communications
Regulatory Compliance
NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in which case
supplementary mitigation measures may be required.
Network
Protocol
Data Rates
EtherNet/IP
10 Mbps Full Duplex, 10 Mbps Half Duplex, 100 Mbps Full Duplex, or 100 Mbps
Half Duplex
Connection Limits 30 TCP connections
16 simultaneous CIP connections including 1 exclusive-owner I/O connection
The following activities use a CIP connection:
Class I I/O connections (for example, from a ControlLogix controller) or
‘Integrated Motion on the EtherNet/IP network’ connection
Explicit messaging where ‘connected’ is chosen (for example, in a check box
in RSLogix 5000 software)
DriveExecutive connections to the drive
The following activities do not use a CIP connection:
Explicit messaging-based control using PCCC or the Register or Assembly
objects
Explicit messaging where ‘connected’ is not chosen, which is typically the
default
DriveExplorer software connections to the drive
Requested Packet Interval (RPI) 2 ms minimum
‘Integrated Motion on the
EtherNet/IP network’ Coarse
Update Rate
2 ms minimum
Packet Rate Up to 400 total I/O packets per second (200 in and 200 out)
Drive
Protocol
Data Rate
DPI
500 Kbps
UL UL508C
cUL CAN / CSA C22.2 No. 14-M91
CE EN50178 and EN61800-3
CTick EN61800-3