Rockwell-automation AADvance Controller Configuration Guide Uživatelský manuál Strana 217

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 286
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 216
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
9-31
Restart a Slave with Ping disabled
1) Configure the salve with a Control Variable Address.
This is the address of the Modbus holding register for the slave link control
variable.
2) Set the Slave control register variable to a 0 (off)
3) Set the control register variable to 2 (active)
The master will restart communication with the slave.
Restart All Active Slaves Associated with a Master
1) Select the Master object.
2) Set a Control Variable Address
This is the address of the Modbus holding register for the control variable.
3) Set the Master Control Variable to 0 (off)
4) Set the Master Control Variable to 2 (active).