Rockwell-automation AADvance Controller Configuration Guide Uživatelský manuál Strana 114

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 286
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 113
5-16
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
About Configuring I/O Channels
The AADvance Workbench provides a set of variable structures to wire to I/O
channels. When you declare the I/O channels variables using your own tagnames you
can declare one of two types of structure (compact and full); alternatively, the primary
variable can be assigned directly to the base variable type.
The AADvance Workbench will automatically generate a set of variable elements with
the same tagname; thus depending on the chosen structure, the system automatically
wires a set of I/O variables to the channels.
The syntax for a structure variable is <tagname>.XX where XX represents the
reporting element of the variable; for example, <tagname>.DI is a Boolean that
reports the digital input state for a channel.
Wire Variables to Digital Input Channels
To wire variables to digital input channels do the following:
1) Select a digital input module on the I/O Bus.
The module status variable <tagname> that you assigned will appear in the
Variable field.
2) Select the channel that you want to wire to a variable.
Zobrazit stránku 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 285 286

Komentáře k této Příručce

Žádné komentáře