Rockwell-automation AADvance Controller Configuration Guide Uživatelský manuál Strana 119

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 286
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 118
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
5-21
<tagname>.STA
USINT
State
Reports a state value for the channel:
1 = open circuit
2 = de-energized
3 = indeterminate
4 = energized
5 = short-circuit
6 = over voltage
7 = faulted
Note: (†) Discrepancy can only be reported TRUE when two or three modules are
active in a group. (††) The voltage element cannot report values below 0mV.
Faulted State for Digital Inputs
A digital input channel is faulted (the state reports a value of 7) when the channel is
incapable of reporting a voltage within a safety accuracy specification of 10% of the full
scale measurement of the 24V dc supply (2.4V).
When the state reports the value 7, then the following 'safe' values are reported by the
other variables:
Input State = FALSE
Line Fault = TRUE
Discrepancy = TRUE
Channel Fault = TRUE
Voltage = 0mV
Zobrazit stránku 118
1 2 ... 114 115 116 117 118 119 120 121 122 123 124 ... 285 286

Komentáře k této Příručce

Žádné komentáře