Document: 553633
ICSTT-RM405f-EN-P
Issue 07
9-27
5) Check that the Ping Interval is suitable for your application.
The ping interval is specified individually for each slave; it defines the maximum
time between each initiation of a Function Code 08 diagnostic message.
Read Holding Register Ping Mode Setting
1) Select the slave link associated with the master object set to RTU protocol.
The editor for the slave link opens.
2) Select the General tab.
3) Check that the Ping Mode has been set for Read Holding Register.
4) Ensure that a Ping Address has been entered.
5) Check that the Ping Interval is suitable for your application.