Publication 2098-RM003A-EN-P October 2001
Command Reference 2-37
Slew Limit Enable/Disable
Format: :aa01Efddcc<cr>
Parameter
Code:
0x01E
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dd Enable/disable control for the gearing slew rate,
where:
0x00: Disable gearing slew rate limits
0x01: Enable gearing slew rate limits.
Minimum
Value:
0x00
Maximum
Value:
0x01
Default: 0x00