Rockwell-automation 2098-DSD-xxx Ultra3000 Host Commands for Serial In Uživatelský manuál Strana 36

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 176
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 35
Publication 2098-RM003A-EN-P October 2001
2-20 Command Reference
Analog Operating Mode
Commands
Analog Position Scale
Analog Position Offset
Format: :aa028fddcc<cr>
Parameter
Code:
0x028
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x08 = Invalid Function Code
Data Fields: dddd Analog position scale, in units of counts/Volt.
Minimum
Value:
0x8001
Maximum
Value:
0x7FFF
Default: 1000
Format: :aa029fddddcc<cr>
Parameter
Code:
0x029
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Analog position offset, in units of milliVolts.
Minimum
Value:
-10000
Maximum
Value:
10000
Default: 0
Zobrazit stránku 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 175 176

Komentáře k této Příručce

Žádné komentáře