136 Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Appendix C EtherNet/IP Objects
Parameter Object
Class Code
Services
Instances (Single-Drive)
Instances (Multi-Drive)
In addition, the parameters for the other DSI devices can be accessed using the
instance-offset encoding shown in the table below:
Hexadecimal Decimal
0x0F 15
Implemented for:
Service Code Class Instance Service Name
0x01 Yes Yes Get_Attribute_All
0x05 Yes No Reset
0x0E Yes Yes Get_Atribute_Single
0x10 No Yes Set_Attribute_Single
0x4B No Yes Get_Enum_String
Instance Description
0Class
1 Drive Parameter 1
...
...
n Drive Parameter n
(1)
(1) n represents the number of parameters in the drive.
n + 1 Adapter Parameter 1
...
...
n + m Adapter Parameter m
(2)
(2) m represents the number of parameters in the adapter.
Instance Description
0Class
1 Adapter Parameter 1
...
...
m Adapter Parameter m
(1)
(1) m represents the number of parameters in the drive.
Instances (Hex.) Instances (Dec.) Single-Drive Mode Multi-Drive Mode
0x0000...0x3FFF 0...16383 Instances 0...16383 in the drive and
adapter
Instances 0...16383 in the adapter
0x4000...0x43FF 16384...17407 Instances 0...1023 in the adapter Instances 0...1023 in the adapter
0x4400...0x47FF 17408...18431 Instances 0...1023 in the drive Instances 0...1023 in Drive 0
0x4800...0x4BFF 18432...19455 Instances 0...1023 in the DSI device Instances 0...1023 in Drive 1
0x4C00...0x4FFF 19456...20479 Instances 0...1023 in the adapter Instances 0...1023 in Drive 2
0x5000...0x53FF 20480...21503 Not supported Instances 0...1023 in Drive 3
0x5400...0x57FF 21504...22527 Not supported Instances 0...1023 in Drive 4