Chapter 1
Getting Started
The 22-COMM-C ControlNet adapter is a communication option
intended for installation into a PowerFlex 40 or PowerFlex 400 drive. It
can also be used with other Allen-Bradley products that support a DSI
communication adapter, such as the DSI External Comms Kit
(22-XCOMM-DC-BASE). The External Comms Kit enables PowerFlex
4 drives (which cannot support an internally-mounted adapter) to
connect to a ControlNet network.
Figure 1.1 Components of the Adapter
Topic Page Topic Page
Components
1-1 Safety Precautions 1-4
Features 1-2 Quick Start 1-5
Compatible Products 1-3 Modes of Operation 1-6
Required Equipment 1-3
Components
➌➍
LEDs are located
on bottom side of
adapter board
Item Component Description
Status Indicators Four LEDs that indicate the status of the ControlNet connection,
DSI, and the adapter. Refer to Chapter 8, Troubleshooting.
DSI Connector A 20-pin, single-row shrouded male header. An Internal Interface
cable is connected to this connector and a connector on the drive.
Channel A Coax Receptacle Channel A BNC connection for the ControlNet cable.
Channel B Coax Receptacle Channel B BNC connection for the ControlNet cable.
1x/5x Operating Mode
Jumper (J7)
Selects Single (1x) or Multi-Drive (5x) mode of operation. Refer to
Setting Operating Mode and Node Address Switches
on page 2-1.
ControlNet Node Address
Switches
Sets a unique node address for the adapter. Refer to Setting
Operating Mode and Node Address Switches on page 2-1.