5-2 Troubleshooting
PORT Status Indicator
State Cause Corrective Actions
Off The adapter is not powered or
is not properly connected to
the drive.
Securely connect the adapter to the drive
using the Internal Interface (ribbon)
cable.
Apply power to the drive (or adapter if
mounted in a DPI External Comms Kit).
Flashing
Red
The adapter is not receiving a
ping message from the drive.
Verify that cables are securely connected
and not damaged. Replace cables if
necessary.
Cycle power to the drive (or adapter if
mounted in a DPI External Comms Kit).
Solid Red The drive has refused an I/O
connection from the adapter.
Another DPI peripheral is
using the same DPI port as
the adapter.
Important: Cycle power to the drive (or
adapter if mounted in a DPI External
Comms Kit) after making the following
correction:
Verify that all DPI cables on the drive are
securely connected and not damaged.
Replace cables if necessary.
Orange The adapter is connected to a
product that does not support
Rockwell Automation DPI
communications.
Connect the adapter to a product that
supports Allen-Bradley DPI
communications (for example, a PowerFlex
70 or PowerFlex 700 drive).
Flashing
Green
The adapter is establishing an
I/O connection to the drive.
No action required.
Solid Green The adapter is properly
connected and is
communicating with the drive.
No action required.