Chapter 2
Installing the Adapter
Chapter 2 provides instructions for installing the adapter in a PowerFlex
7-Class drive. This adapter can also be installed in a DPI External
Comms Kit. In this case, refer to the 20-XCOMM-DC-BASE Installation
Instructions (Publication No. 20COMM-IN001…) supplied with the kit.
Before installing the adapter, verify that you have all required
equipment. Refer to Required Equipment
on page 1-3.
To commission the adapter, you must set a unique MAC address and,
depending on where the PowerFlex drive nodes are located on the
network (starting and ending network nodes versus other node
locations), appropriately set the TERM, -BIAS, and +BIAS switches.
Important: New settings are recognized only when power is applied to
the adapter or it is reset. If you change a switch setting,
cycle power or reset the adapter to invoke the change.
Topic Page
Preparing for an Installation
2-1
Commissioning the Adapter 2-1
Connecting the Adapter to the Drive 2-6
Applying Power 2-8
Connecting the Drive/Adapter to the Network 2-10
Preparing for an Installation
Commissioning the Adapter
!
ATTENTION: Risk of equipment damage exists. The adapter
contains ESD (Electrostatic Discharge) sensitive parts that can be
damaged if you do not follow ESD control procedures. Static control
precautions are required when handling the adapter. If you are
unfamiliar with static control procedures, refer to Guarding Against
Electrostatic Damage, Publication 8000-4.5.2.