Installing the Adapter 2-7
4. Secure and ground the adapter to the drive by doing the following:
On a PowerFlex 70 drive, fold the Internal Interface cable behind
the adapter and mount the adapter on the drive using the four
captive screws.
On a PowerFlex 700 or PowerFlex 700H drive, just mount the
adapter on the drive using the four captive screws.
Important: Tighten all screws since the adapter is grounded via the
screws. Recommended torque is 0.9 N-m (8.0 lb.-in.).
Figure 2.6 Mounting and Grounding the Adapter
All Frame Sizes:
Adapter mounts in drive.
PowerFlex 70 Drive
Internal Interface Cable
folded behind the adapter
and in front of the drive.
Frames 0 and 1:
Adapter mounts on door.
PowerFlex 700 Drive
Frames 2 and Larger:
Adapter mounts in drive.
Drive
Adapter