BACnet MS/TP
Adapter
20-COMM-B
FRN 1.xxx
User Manual
Zobrazit stránku 0
1 2 3 4 5 6 ... 75 76

Shrnutí obsahu

Strany 1 - BACnet MS/TP

BACnet MS/TP Adapter20-COMM-BFRN 1.xxxUser Manual

Strany 2 - Important User Information

1-2 Getting Started The 20-COMM-B BACnet MS/TP adapter features the following:• The adapter is normally mounted in the PowerFlex 7-Class drive. It c

Strany 3 - Summary of Changes

Getting Started 1-3 The 20-COMM-B BACnet MS/TP adapter is compatible with most Allen-Bradley PowerFlex 7-Class (Architecture-Class) drives and other

Strany 4

1-4 Getting Started Please read the following safety precautions carefully. Safety Precautions!ATTENTION: Risk of injury or death exists. The Powe

Strany 5 - Table of Contents

Getting Started 1-5 !ATTENTION: Risk of injury or equipment damage exists. Parameter 03 - [Comm Loss Time] lets you determine how long it will take

Strany 6

1-6 Getting Started This section is provided to help experienced users quickly start using the adapter. If you are unsure how to complete a step, re

Strany 7 - About This Manual

Getting Started 1-7 The adapter uses four status indicators to report its operating status. They can be viewed on the adapter or through the drive c

Strany 8 - Rockwell Automation Support

1-8 Getting Started Notes:

Strany 9 - Getting Started

Chapter 2Installing the AdapterChapter 2 provides instructions for installing the adapter in a PowerFlex 7-Class drive. This adapter can also be in

Strany 10 - Features

2-2 Installing the Adapter Setting the MAC AddressSet the MAC address using the MAC Address switches (Figure 2.1). Refer to Table 2.A for specific M

Strany 11 - Required Equipment

Installing the Adapter 2-3 8 0 0 0 1 0 0 0 56 0 0 0 1 1 1 09 1 0 0 1 0 0 0 57 1 0 0 1 1 1 010 0 1 0 1 0 0 0 58 0 1 0 1 1 1 011 1 1 0 1 0 0 0 59 1 1

Strany 12 - Safety Precautions

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

Strany 13

2-4 Installing the Adapter Setting the TERM, -BIAS, and +BIAS SwitchesThe adapter’s TERM, -BIAS, and +BIAS switches (Figure 2.2) are used to turn on

Strany 14 - Quick Start

Installing the Adapter 2-5 Network with PowerFlex Drives at Starting and/or Ending NodesFor a network with PowerFlex drives at the starting and/or e

Strany 15 - Status Indicators

2-6 Installing the Adapter 1. Remove power from the drive.2. Use static control precautions, and remove or open the drive cover.3. Connect the Inter

Strany 16 - 1-8 Getting Started

Installing the Adapter 2-7 4. Secure and ground the adapter to the drive by doing the following:– On a PowerFlex 70 drive, fold the Internal Interfa

Strany 17 - Installing the Adapter

2-8 Installing the Adapter Install or close the drive cover, and apply power to the drive. The adapter receives its power from the connected drive.

Strany 18 - Setting the MAC Address

Installing the Adapter 2-9 Table 2.B Drive and Adapter Start-Up Status Indications Verifying/Setting Key Adapter ParametersTo access adapter para

Strany 19 - Installing the Adapter 2-3

2-10 Installing the Adapter Configuring/Verifying Key Drive ParametersThe PowerFlex 7-Class drive can be separately configured for the control and r

Strany 20 - Reserved for future use

Installing the Adapter 2-11 Figure 2.8 Typical Network Terminal Connections 5. Insert the 3-pin linear plug into the mating adapter socket.6. Ins

Strany 21

2-12 Installing the Adapter Notes:

Strany 22 - 2-6 Installing the Adapter

Chapter 3Configuring the AdapterChapter 3 provides instructions and information for setting the parameters in the adapter. For a list of parameter

Strany 23 - PowerFlex 700 Drive

Summary of ChangesThe information below summarizes the changes made to this manual since its last release (May 2006): The information below summar

Strany 24 - Applying Power

3-2 Configuring the Adapter If your drive has either an LED or LCD HIM (Human Interface Module), you can use it to access parameters in the adapter

Strany 25

Configuring the Adapter 3-3 While there are many ways to implement Device Instance and network strategies, the example shown in Figure 3.1 illustrat

Strany 26

3-4 Configuring the Adapter 1. Set the value of Parameter 11 - [Device Instance] to a unique Device Instance Number.Figure 3.2 Device Instance Scr

Strany 27 - -A Signal A TxRxD

Configuring the Adapter 3-5 By default, when communications are disrupted (for example, a cable is disconnected), the drive responds by faulting if

Strany 28 - 2-12 Installing the Adapter

3-6 Configuring the Adapter To set the fault configuration parametersIf you set Parameter 02 - [Comm Loss Action] to “Send Flt Cfg,” the values in t

Strany 29 - Configuring the Adapter

Configuring the Adapter 3-7 The value of Parameter 06 - [Baud Rate Cfg] determines the baud rate used by the adapter. The Autobaud setting will dete

Strany 30 - Using an LCD HIM

3-8 Configuring the Adapter When you enter 1 = Reset Module, the adapter will be immediately reset. When you enter 2 = Set Defaults, the adapter wil

Strany 31 - Building Level Network 2

Chapter 4Using BACnet ObjectsChapter 4 provides information about controlling a compatible PowerFlex 7-Class drive using BACnet objects. BACnet no

Strany 32 - Device Instance Number

4-2 Using BACnet Objects This section describes how to operate a drive on the network using a combination of BACnet object types for basic control.

Strany 33 - Setting a Comm Loss Action

Using BACnet Objects 4-3 The type of drive used on the network determines the specific BACnet objects that are supported. Refer to Table 4.A for des

Strany 35 - Resetting the Adapter

4-4 Using BACnet Objects Table 4.A BACnet Object Descriptions and Supported Drives (Continued)Object Name Use This Object to…Compatible PowerFlex

Strany 36

Using BACnet Objects 4-5 Table 4.A BACnet Object Descriptions and Supported Drives (Continued)Object Name Use This Object to…Compatible PowerFlex

Strany 37 - Using BACnet Objects

4-6 Using BACnet Objects Table 4.A BACnet Object Descriptions and Supported Drives (Continued)Object Name Use This Object to…Compatible PowerFlex

Strany 38 - Clearing a Drive Fault

Chapter 5TroubleshootingChapter 5 provides information for diagnosing and troubleshooting potential problems with the adapter and network. The ada

Strany 39 - Supported BACnet Objects

5-2 Troubleshooting PORT Status IndicatorState Cause Corrective ActionsOff The adapter is not powered or is not properly connected to the drive.• S

Strany 40 - 4-4 Using BACnet Objects

Troubleshooting 5-3 MOD Status IndicatorState Cause Corrective ActionsOff The adapter is not powered or is not properly connected to the drive.• Sec

Strany 41 - Using BACnet Objects 4-5

5-4 Troubleshooting NET A Status IndicatorState Cause Corrective ActionsOff The adapter is not powered or is not properly connected to the network.•

Strany 42 - 4-6 Using BACnet Objects

Troubleshooting 5-5 The following adapter diagnostic items can be viewed using DriveExplorer (version 3.01 or higher) or DriveExecutive (version 3.0

Strany 43 - Troubleshooting

5-6 Troubleshooting Adapter Diagnostic ItemsIf you encounter unexpected communications problems, diagnostic items can help you or Rockwell Automatio

Strany 44 - PORT Status Indicator

Troubleshooting 5-7 The adapter maintains an event queue that reports the history of its actions. You can view this event queue using an LCD PowerFl

Strany 45 - MOD Status Indicator

Table of ContentsPreface About This ManualRelated Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1Rockwell Automation S

Strany 46 - NET B Status Indicator

5-8 Troubleshooting EventsMany events in the Event queue occur under normal operation. If you encounter unexpected communications problems, the even

Strany 47 - Troubleshooting 5-5

Appendix ASpecificationsAppendix A presents the specifications for the adapter.Topic PageCommunicationsA-1Electrical A-1Mechanical A-1Environmental

Strany 48 - Adapter Diagnostic Items

A-2 Specifications NOTE: This is a product of category C2 according to IEC 61800-3. In a domestic environment this product may cause radio interfere

Strany 49 - Viewing and Clearing Events

Appendix BAdapter ParametersAppendix B provides information about the BACnet MS/TP adapter parameters. The parameters in the adapter are numbered

Strany 50 - 5-8 Troubleshooting

B-2 Adapter Parameters 02 [Comm Loss Action]Sets the action that the adapter and drive will take if the adapter detects that network communications

Strany 51 - Specifications

Adapter Parameters B-3 07 [Baud Rate Act]Displays the baud rate (kilobits per second) actually used by the adapter.Default: 0 = UnknownValues: 0 = U

Strany 52 - Regulatory Compliance

B-4 Adapter Parameters Notes:

Strany 53 - Adapter Parameters

Appendix CProtocol Implementation Conformance Statement (PICS)Date: March 27, 2006Vendor Name: Rockwell AutomationProduct Name: 20-COMM-BProduct Mo

Strany 54 - B-2 Adapter Parameters

C-2 Protocol Implementation Conformance Statement (PICS) Standard Object Types SupportedThe table below lists the object types supported by the 20-C

Strany 55 - Adapter Parameters B-3

Protocol Implementation Conformance Statement (PICS) C-3 Data Link Layer Options BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 88

Strany 56 - B-4 Adapter Parameters

ii Table of Contents Chapter 5 TroubleshootingUnderstanding the Status Indicators . . . . . . . . . . . . . . . . . . . 5-1PORT Status Indicator .

Strany 57 - Conformance Statement (PICS)

C-4 Protocol Implementation Conformance Statement (PICS) Notes:

Strany 58

Appendix DRouting Capability for Networked DrivesAppendix D provides information about the unique routing capability for up to 127 PowerFlex 7-Clas

Strany 59 - Networking Options

D-2 Routing Capability for Networked Drives Notes:

Strany 60

GlossaryA AdapterDevices such as drives, controllers, and computers usually require an adapter to provide a communication interface between them an

Strany 61 - Appendix D

Glossary-2 DPI PeripheralA device that provides an interface between DPI and a network or user. Peripheral devices are also referred to as “adapters

Strany 62

Glossary-3 user-defined fault configuration. The user sets the data that is sent to the drive using specific fault configuration parameters in the a

Strany 63 - Glossary

Glossary-4 from the adapter to the network. The definitions of the bits in this word depend on the drive.M MAC AddressEach device on a network must

Strany 64 - F Fault Action

Glossary-5 S Status IndicatorsStatus indicators are LEDs that are used to report the status of the adapter, network, and drive. They are on the adap

Strany 66 - R Reference/Feedback

IndexNumerics3-pin linear plug, 2-11Aadapterapplying power, 2-8commissioning, 2-1compatible products, 1-3components, 1-1connecting to a drive, 2-6c

Strany 67 - Z Zero Data

PrefaceAbout This ManualDocumentation can be obtained online at http://www.rockwellautomation.com/literature.Topic PageRelated DocumentationP-1Rock

Strany 68 - Glossary-6

Index-2 EEDS (Electronic Data Sheet) filesdefinition, G-2web site, G-2EEPROM, see Non-Volatile Storage (NVS)electrical specifications, A-1environmen

Strany 69 - Numerics

Index-3 NET B status indicatorlocating, 1-7troubleshooting with, 5-4network cable - connecting to 3-pin plug, 2-11Non-Volatile Storage (NVS)accessin

Strany 70

Index-4 Wweb siteDriveExecutive software, G-2DriveExplorer software, G-2DriveTools SP software, G-2EDS files, G-2PowerFlex manuals, P-1Zzero datacon

Strany 71

Index-5 Notes:

Strany 72

Index-6 Notes:

Strany 74

www.rockwellautomation.comAmericas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 4

Strany 75

P-2 About This Manual Rockwell Automation, Inc. offers support services worldwide, with over 75 sales/support offices, over 500 authorized distribut

Strany 76

Chapter 1Getting StartedThe 20-COMM-B BACnet MS/TP adapter is a communication option intended for installation into a PowerFlex 7-Class drive. It c