4-6 Using BACnet Objects
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object Name Use This Object to…
Compatible PowerFlex Drives
70 Std. 70 EC 700 Std. 700 VC 700 H
BV2 Running Reverse Read the drive’s Running Reverse status, which is active if the drive is
running in the reverse direction.
✔✔ ✔✔
BV3 Fault Read the drive’s Fault status, which is active if the drive is faulted. ✔✔ ✔✔
BV4 Alarm Read the drive’s Alarm status, which is active if the drive has an
alarm.
✔✔ ✔✔
BV5 At Reference Read the drive’s At Reference status, which is active if the drive is
running at the specified speed reference.
✔✔ ✔✔
BV10 Run/Stop Read/write the adapter’s Run/Stop command. Turn on this object to
start the drive. Turn off this object to stop the drive.
✔✔ ✔✔
BV11 Rev/Fwd Read/write the adapter’s Rev/Fwd command. Turn on this object to
command the reverse direction when the drive is running. Turn off this
object to command Forward.
✔✔ ✔✔
BV12 Ref2/Ref1 Read/write the adapter’s Ref2/Ref1 command. Turn on this object to
select the Reference 2 instance of the AV object as the drive’s speed
reference. Turn off this object to select Reference 1. The drive must
be configured to accept its speed reference from the network. This is
typically done by setting drive parameter 90 - [Speed Ref A Sel] to the
value “22” (DPI Port 5).
✔✔ ✔✔
BV13 Clear Faults Read/write the adapter’s Clear Faults command. Turn on this object
to clear the drive fault. Turning off this object does nothing.
✔✔ ✔✔