Rockwell-automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter Uživatelský manuál Strana 54

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 204
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 53
Publication 1769-UM001B-EN-P - October 2002
3-4 Configuring Your Compact I/O Series A DeviceNet Adapter
2. Continue to list your devices down the left column and continue
at the top right column if necessary.
Note: To limit the need to reconfigure, make sure you
understand the Configuration Rules for the Series A Adapter on
page 3-7.
Notice that only I/O modules are assigned Slot numbers.
3. Once you’ve listed all of the devices for Bank 1, go on to Bank 2
if necessary.
Note: A second I/O bank may be necessary if your bank 1
power supply has an insufficient power budget for the I/O
modules required for your application.
Note: Make sure your bank-to-bank expansion cable (e.g.
1769-CRR1) is in the last component of bank 1.
Zobrazit stránku 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 203 204

Komentáře k této Příručce

Žádné komentáře