B-4 Explicit Messaging Application Examples
Get 1769 I/O Module Status
Use a “CIP Generic” MSG instruction to send the Get 1769 I/O Module
Status explicit message from a Logix5550 controller via a 1756-DNB
scanner on DeviceNet. You’ll see in the ladder logic example to
follow, a CIP Generic message is sent to the 1756-DNB scanner and
ultimately to the 1769-ADN and the 1769 I/O module in slot 10.
Use a “Single Parameter Read” MSG instruction for the Get 1769 I/O
Module Status message, where one word of status information is read
from the 1769 I/O module in slot 10. The user program consists of a
single rung containing a MSG instruction to accomplish the Get 1769
I/O Module Status.
The following correlates the CIP Generic message terminology with
DeviceNet command terminology and illustrates the values needed
specifically for the Get 1769 I/O Module Status message:
Values (Hexadecimal) DeviceNet Terminology CIP Generic Terminology
e Service
1
Service Code
30c Class
2
Object Type
10 (decimal) Instance
3
Object ID
c Attribute
4
Object Attribute
1 Service specifies the type of request being delivered. “e” hexadecimal is a “Single Parameter Read”.
2 Class specifies the desired DeviceNet class. “30c” hexadecimal is the class code for the object representing
1769 I/O.
3 Instance represents the slot number of the I/O module from which we want status information. “10” decimal
in this example is the analog output module in slot 10.
4 Attribute identifies the specific characteristics of the object towards which the transaction is directed.
“c” hexadecimal means Module Status.