B-20 Explicit Messaging Application Examples
The following ladder logic program is an example of the logic needed
to initiate an explicit message to the scanner/adapter/1769 I/O
module and how to obtain the reply. This logic is specifically for the
Get 1769 I/O Module Status command. Assume the 1747-SDN scanner
is in slot 3 of the processor chassis and the 1769-OF2 module that we
are reading status from is in slot 10 of the 1769-ADN remote system.
Data Table File N11 (Shown in Hexadecimal Radix)
Offset0123456789
N11:01016E1330CAC0000
N11:100000000000
N11:200000000000
N11:300000000000
N11:404000000000
N11:50 101 1 8E13 4000000
Zobrazit stránku 177