Rockwell-automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter Uživatelský manuál Strana 36

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 204
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 35
Publication 1769-UM001B-EN-P - October 2002
2-12 How Communication Takes Place and I/O Image Table Mapping
1769-OV16 Solid State 24V
DC Sink Output Module
(16 Point)
Output Data
For each 1769-OV16 module, output data word 0 contains the control
program’s directed state of the discrete output points.
Input Data
For each 1769-OV16 module, input data word 0 contains the state of
the module’s output data (output data echo) word 0. During normal
operation (controller in Run), these input bits represent the logic state
that the outputs are directed to by the control program. They are also
dependent upon the:
Program Mode configuration (Hold Last or User-Defined Safe
State)
Fault Mode configuration (Hold Last or User-Defined Safe State)
Word
Bit Position
1514131211109876543210
0wwwwwwwwwwwwwwww
w = write
Word
Bit Position
1514131211109876543210
0rrrrrrrrrrrrrrrr
r = read
IMPORTANT
The output module’s input data reflects the output
data echo of the module, not necessarily the
electrical state of the output terminals. It does not
reflect shorted or open outputs.
Zobrazit stránku 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 203 204

Komentáře k této Příručce

Žádné komentáře