Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-73
10. actual value equal to zero
11. out of value range
Range A:
The counter has the value zero.
The contacts C..ZE (actual value equal to zero) and C..FB (lower set
point value undershot) are active.
The counter receives counter values and increases the actual value.
C..ZE drops out as well as C..FB and also when the lower set point
value is reached.
Range B:
The counter counts upwards and reaches the upper set point value.
The “upper set point value reached” contact C..OF becomes active.
Range C:
The coil C..SE is briefly actuated and the actual value is set to the
preset actual value. The contacts go to the respective position.
Range D:
The counting direction coil C..D_ is actuated. If counting pulses are
present, downward count is initiated.
If the lower set point value is undershot, the contact C..FB becomes
active.
Range E:
The reset coil C..RE is activated. The actual value is set to zero.
The contact C..ZE is active.
Range F:
The actual value goes outside the value range of the counter.
The contacts become active according to the direction of the values
(positive or negative).