Troubleshooting the Module and Network
8-5
8.1.4 NET B Status Indicator
Table 8.5 – NET B Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is not
powered or is not
transmitting on the
EtherNet/IP
network.
If Net A is off:
Securely connect the module to
the drive using the Internal
Interface cable and to the
network using an Ethernet
cable.
Correctly connect the Ethernet
cable to the Ethernet connector.
Set a unique IP address using a
BOOTP server or by disabling
BOOTP and using parameters.
If Net A is solid Red:
Configure the module to use a
unique IP address and cycle
power.
If Net A is flashing red/green or
red:
Check the IP address in the
module and scanner.
Ping the module.
Normal condition if the module is
idle.
Flashing
Green
The module is
transmitting on the
EtherNet/IP
network.
No action required.