Configuring Enhanced PLC-5 Processors 2-27
Figure 2.6 Example of a PLC-5 Write MSG to Another PLC-5
(or SLC 5/03, 5/04, 5/05, MicroLogix 1100/1200/1500, or Logix) Processor
This MSG example tells this (master) PLC-5 to write the information
from its file N19:0 through its serial port (channel 0) to the PLC-5
(slave) station 13
8
. The data’s destination is N7:0 of the PLC-5 (slave)
station.
Ladder Rung
Control Block
MSG being sent to another
PLC-5 processor.
MSG being sent out channel
0 (must use MG file type).
If the destination were a
Logix processor, then the
address could also be
entered as “tagname”.