Publication AG-UM008C-EN-P - February 2005
4-10 Configuring SLC 5/03, 5/04, and 5/05 Processors
Configuring a
Standard-Mode DF1
Half-Duplex Master Station
Choose standard mode if you want to query slave stations for
information based upon user-configured polling ranges. This mode is
used most often in general point-to-multipoint configurations.
To configure the processor for a master station using standard
communication, place the processor into program mode and follow
the steps below using your programming software:
1. To bring up the Channel
Configuration interface,
double-click on the Channel
Configuration icon.
2. Define the location of the
diagnostic file used for
Channel Status here. For
Channel Status details, see
page 4-16.