Publication AG-UM008C-EN-P - February 2005
Configuring SLC 5/03, 5/04, and 5/05 Processors 4-45
This MSG example tells the SLC 5/03, 5/04, or 5/05 master station to
read the information from PLC-5 slave station 11
10
’s N19:1 and place
the information in master station file N9:0. For a Logix slave station, a
tag name would have to already have been mapped to N19.
Alternatively, SLC 5/03 (OS 302 C or higher), 5/04 (OS 401 C or
higher) and 5/05 processors support logical ASCII addressing, which
means any Logix controller tag can be read by entering the tag name
in double quotes in the Target’s Data Table Address field.
Figure 4.8 Write MSG from an SLC 5/03, 5/04, or 5/05 Processor to Another SLC 500
or a MicroLogix Controller
MSG being sent to another
SLC 500 or a MicroLogix
controller