Rockwell-automation 592- E300 Overload Relay User Manual Uživatelský manuál Strana 94

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 424
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 93
94 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Table 75 - Ground Fault Trip Delay (Parameter 243)
Ground Fault Trip Level
Ground Fault Trip Level (Parameter 244) allows the user to define the ground
fault current in which the E300 Electronic Overload Relay will trip and is
adjustable from:
0.500…5.00 A (In
ternal)
0.020…5.00 A (Ext
ernal)
Table 76 - Ground Fault Trip Level (Parameter 244)
Ground Fault Warning
The E300 Electronic Overload Relay will indicate a ground fault warning if:
No warning currently exists
Ground Fault Warning is enabled
Current is present
Ground Fault Inhibit Time has expired
Ground Fault Trip Delay (Parameter 243)
Default Value 0.5
Minimum Value 0.0
Maximum Value 25.0
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 10
Units Sec
Ground Fault Trip Level (Parameter 244)
Default Value 2.5
Minimum Value 0.5 (internal); 0.02 (external)
Maximum Value 5.00
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 100
Units Amps
IMPORTANT
The ground fault inhibit timer starts after the maximum phase load current
transitions from 0 A to 30% of the devices minimum FLA rating or the ground
fault current is greater than or equal to 50% of the devices minimum ground
fault current rating. The E300 Electronic Overload Relay does not begin
monitoring for a ground fault condition until the Ground Fault Current Inhibit
Time expires.
Zobrazit stránku 93
1 2 ... 89 90 91 92 93 94 95 96 97 98 99 ... 423 424

Komentáře k této Příručce

Žádné komentáře