Rockwell Automation Publication 193-UM015B-EN-P - June 2014 273
Metering and Diagnostics Chapter 7
Warning History Mask
Users can decide which warning events are recorded into the E300 Electronic
Overload Relays warning history by using the Warning History Masks.
Current Warning History Mask
Current Warning History Mask (Parameter 145) allows users to select which
current based warning events are recorded in the warning history.
Table 322 - Current Warning History Mask (Parameter 145)
Voltage Warning History Mask
Voltage Warning History Mask (Parameter 146) allows users to select which
voltage based warning events are recorded in the warning history.
88 Analog Expansion Module 4 is not operating properly
90 Control Module installed does not match the expected type
91 Sensing Module installed does not match the expected type
92 Comms Module installed does not match the expected type
93 Operator Station installed does not match expected type
94 Digital Module installed does not match the expected type
95 Analog Module installed does not match the expected type
98 A hardware fault condition was detected
Warning History Code Description
Bit
1514131211109876543210 Function
X
Overload Warning
Reserved
X
Ground Fault Warning
Reserved
X
Jam Warning
X
Underload Warning
X
Current Imbalance Warning
X
L1 Under Current Trip
X
L2 Under Current Trip
X
L3 Under Current Trip
X
L1 Over Current Trip
X
L2 Over Current Trip
X
L3 Over Current Trip
X
L1 Line Loss Trip
X
L2 Line Loss Trip
X
L3 Line Loss Trip