Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 27
Product Overview Chapter 1
internal resistor monitoring circuit board. The cable length available is 0.5 m and
1.0 m. The IP67 Dynamic Brake is separately ordered. See Chapter 11
for
available IP67 Dynamic Brake Resistors.
Note: The IP67 Dynamic Brake Resistor is used only with the -DB1
factory-installed option. Only the specified IP67 Dynamic Brake resistor
can be used based on the VFD horsepower. Connecting resistors other than those
specified will result in a DB1 fault.
Output Contactor (Bulletin 284E only)
An internal contactor is sourced from the 24V DC (A1/A2) control voltage
to isolate the load side of the Bulletin 284E ArmorStart Distributed Motor
Controller. When control power is applied to A1/A2, the output contactor will
close. When control power is removed, the output contactor will open. There is
no other switching element that allows alternate control of the output contactor.
A sequenced stop involving the output contactor cannot be performed.
Shielded Motor Cable (Bulletin 284E only)
If the EMI Filter is selected, a 3-meter shielded 4-conductor cordset is provided
as standard.