120 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Starter Enclosure
Bit 0 = IP67
Bit 1 = Reserved
Bit 2 = Sil3/Cat4
Bit 3…15 = Reserved
Parameter Number 59
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 4
Default Value 1
Starter Options
Bit 0 = Full Keypad
Bit 1 = Reserved
Bit 2 = Source Brake
Bit 3 = Reserved
Bit 4 = Reserved
Bit 5 = Reserved
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Reserved
Bit 9…15 = Reserved
Parameter Number 60
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 66535
Default Value 0
Last PR Fault
0 = None
1 = Hardware Short Circuit
2 = Software Short Circuit
3 = Motor Overload
4 = Reserved
5 = Phase Loss
6…12 = Reserved
13 = Control Power Loss
14 = Control Power Fuse
15 = I/O Short
16 = Output Fuse
17 = Overtemp
18 = Reserved
19 = Phase Imbalance
20 = Reserved
21 = A3 Power Loss
22 = Internal Comm
23…26 = Reserved
27 = MCB EEPROM
28 = Base EEPROM
29 = Reserved
30 = Wrong Base
31 = Wrong CTs
32…100 = Reserved
Parameter Number 61
Access Rule GET
Data Type UINT
Group Basic Status
Units
Minimum Value 0
Maximum Value 100
Default Value 0