150 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Miscellaneous Configuration Group
OutB Net FltValue
This parameter determines the state
that Output B assumes when a
network fault occurs and Parameter
41 (OutB Net FltState) is set to “0”.
0 = Open
1 = Close
Parameter Number 42
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutB Net IdlState
This parameter in conjunction with
Parameter 44 (OutB Net IdlValue)
defines how Output B will respond
when the network is idle.
0 = Goto PrFlt Value
1 = Ignore PrFlt
When set to “0”, Output B will open or
close as determined by the setting in
Parameter 44.
Parameter Number 43
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutB Net IdlValue
This parameter determines the state
that Output B assumes when the
network is idle and Parameter 43
(OutB Net IdlState) is set to “0”.
0 = Open
1 = Close
Parameter Number 44
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Network Override
This parameter allows for the local
logic to override a Network fault.
0 = Disable
1 = Enable
Parameter Number 8
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0