132 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Starter Setup Group (Bulletin 280E/281E only)
FLA Setting
The motor’s full load current rating is
programmed in this parameter.
Parameter Number 106
Access Rule GET/SET
Data Type INT
Group Starter Setup
Units xx.x Amps
Minimum Value See Table19.
Maximum Value See Table19.
Default Value See Table19.
Table 19 - FLA Setting Ranges and Default Values (with indicated setting precision)
FLA Current Range (A)
Default Value
Minimum Value Maximum Value
0.24 1.2 0.24
0.5 2.5 0.5
1.1 5.5 1.1
3.2 16.0 3.2
Overload Class
This parameter allows the installer to
select the overload class.
1 = Overload Class 10
2 = Overload Class 15
3 = Overload Class 20
Parameter Number 107
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units xx.x Amps
Minimum Value 1
Maximum Value 3
Default Value 1
OL Reset Level
This parameter allows the installer
select the % Thermal Capacity which
an overload can be cleared.
Parameter Number 108
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 75