Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013 31
Chapter 4
Configuring the PROFIBUS Master
PROFIBUS masters are available from several manufacturers, including ProSoft
Technology. This chapter provides instructions on how to use the MVI69-
PDPMV1 PROFIBUS DPV1 master and do the following:
• Configure the MVI69-PDPMV1 PROFIBUS DPV1 master.
• Install the 25-COMM-P GSD file in the software tool library.
• Configure the 25-COMM-P adapter as a PowerFlex 520-series
PROFIBUS slave.
Example Network
In this example, we will configure one PowerFlex 520-series drive, with an
installed 25-COMM-P adapter, to be assigned as Station 1 on a PROFIBUS
network. This configuration is used as an example system throughout this
manual. Apart from the node address and adapter mapping, most drives will have
identical configurations. This chapter describes the steps to configure a simple
PROFIBUS network like the example shown in Example PROFIBUS Network
on page 31.
When using a ControlLogix or CompactLogix controller, the Endianness switch
of the adapter must be set to OFF ‘0’ (Little Endian). See Setting the Endianness
and Node Address Using the DIP Switches on page 14 for more information.
Example PROFIBUS Network
Topic Page
Example Network
31
Configuring the MVI69-PDPMV1 PROFIBUS DPV1 Master 32
Installing GSD Files 34
Configuring the Adapter as a Slave 36
PROFIBUS
CompactLogix controller with
MVI69-PDPMV1 in slot 1
Master
PowerFlex 520-series drive
with 25-COMM-P
Address 3