Using Explicit Messaging Chapter 6
Figure 73 - Example Ladder Logic to Write Multiple Parameters
Important:If the explicit message scattered write must be written
continuously, then use a separate Generic Set service explicit
message single write for each parameter using DPI Parameter
Object Class code 0x93 and attribute A (10 decimal; see
page 133
). Attribute A writes to RAM—not NVS (EEPROM)
memory. This example scattered write message using attribute 0
writes to NVS. Over time, continuous writes will exceed the
EEPROM life cycle and cause the drive to malfunction.
MicroLogix 1100/1400 Controller – Formatting a Message to Write Multiple
Parameters Using Generic Get/Set Attribute Service
Figure 74 - Custom Scattered Write Multiple Message Configuration Screens