Rockwell-automation 1797-OE8H FLEX Ex HART Analog Modules User Manual Uživatelský manuál Strana 97

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 196
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 96
Publication 1797-6.5.3 - March 2006
Calibrate Your Module 5-21
1797-OE8H Calibration Flowchart Procedure
Perform the calibration at ambient room temperature, 25 (±5) °C, according
to the procedure flowchart. Each channel is calibrated one after the other. The
current is measured indirectly via a precision voltmeter placed across a
precision 100 ohm resistor.
Before all values are completely calibrated, a calibration error is displayed
within the Real Time Data field in the diagnostic status field. After calibration
is complete, the I/O module stores the calibrated values in the RAM area.
Therefore, you must send a store command to cause the I/O module to
transfer the RAM content to the EEPROM.
+-CHx
100 ohm 650 ohm
Voltmeter
Voltmeter
Zobrazit stránku 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 195 196

Komentáře k této Příručce

Žádné komentáře