Publication 1797-6.5.3 - March 2006
2-18 Understand Configurable FLEX Ex Analog Module Features
Table 2.16 Data Format Control
Data
Format
Range Resolution Full
Range
Interpretation Data Table
Value
Count per
mA
00000…20 mA0.1% of
0…20 mA
0…22 mA 0…22 mA 0…2000 1000
0001 0.2% of
0…20 mA
0…110% 0…11000 500
0010Not assigned
00114…20 mA0.03% of
0…20 mA
0…20 mA Unsigned
integer
0…65535 3276
0100 0.1% of
4…20 mA
2…22 mA 2…22 mA 2000…
22000
1000
0101Not assigned
0110
01114…20 mA0.03% of
4…20 mA
4…20 mA Unsigned
integer
0…65535 4095
1000Not assigned
1001
1010
10110…20 mA0.28% of
0…20 mA
0…22 mA D/A count 0…8000 363
1100Not assigned
11014…20mA0.16% of
4…20 mA
3…21 mA -6.25…
+106.25%
-625…
+10625
625
1110 2…22 mA-12.5…
+112.5%
-1250…
+11250
625
1111Not assigned