Publication 1797-6.5.3 - March 2006
FLEX Ex HART Module Commands B-7
Command 131
For the given long frame addresses, the Read Static Data of Transmitters
command returns the following transmitter data:
Current loop number, 0 to 15
Polling address
Supported HART revision
Minimum count of required preambles, 5 to 20
There are no request data bytes.
Table B.6 Command 131 Response Data Bytes
Byte Description Value
Response Data Bytes
0…4 EXT_ADDR_0 Extended address of instrument 0
5 ERROR_0 Error 0 0 = Instrument
present. Data for
that instrument is
included in reply.
64 = Unknown
instrument. Data
for that
instrument is not
included in reply.
EXT_ADDR_I Extended address I
ERRO_I Error I
……
Command-specific Response Codes
16 Error Access restricted
32 Error Busy
Zobrazit stránku 130