FM I/O Entity Parameters for 1797-OE8
FM I/O Entity Parameters for 1797-OE8H
Wiring
Method
Channel Term inals V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups C
a
(μF)
L
a
(mH)
1 and 2 Any one
channel
(for
example,
ch0)
0(+), 1(sig) 21.0 100.0 - - A, B 0.20 3.5
C, E 0.60 10.5
D, F, G 1.60 28.0
Wiring
Method
Channel Terminals V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups C
a
(μF)
L
a
(mH)
1 and 2 Any one
channel
(for
example,
ch0)
0(+), 1(sig) 21.6 92 - - A, B 0.164 3.5
C, E 0.49 10.5
D, F, G 1.31 28.0