42 FLEX Ex 8 Output and HART Analog Modules
Publication
1797-5.3 - September 2011
Table 1
Wiring
Method
Channel Terminals V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups C
a
(μF)
L
a
(mH)
1 and 2 Any one
channel
(for
example,
ch0)
0(+), 1(-) 21.0 100.0 - - A, B, IIC 0.08 2.0
C, E, IIB 0.24 8.0
D, F, G,
IIA
0.64 16.0
A terminal base may or may not have an I/O module
installed.
FLEX Ex Analog
Output I/O
Indicators
Female Bus
Field Wiring
Terminal Base
Term inal Base
Key
Male Bus
Connection
Key Position for
Terminal Base
Insertion
42013