CIP/DSI Objects C-15
Class Attributes (Continued)
Instance Attributes
DSI Fault Object (Continued)
Attribute
ID
Access
Rule
Name Data Type Description
5 Get Fault Data List STRUCT of:
BYTE
BYTE
WORD[n]
Reserved
6 Get Number of
Recorded Faults
WORD Number of faults/events in the queue. A
“0” indicates the fault queue is empty.
7 Get Fault Parameter
Reference
WORD Reserved
Attribute
ID
Access
Rule
Name Data Type Description
0 Get Full/All
Information
STRUCT of:
WORD
STRUCT of:
BYTE
BYTE
STRING[16]
STRUCT of:
LWORD
BOOL[16]
WORD
CONTAINER[n]
Fault code
Fault source
DSI port
DSI Device Object
Fault text
Fault time stamp
Timer value (0 = Timer not supported)
BOOL[0]: (0 = invalid data, 1 = valid data)
BOOL[1]: (0 = elapsed time, 1 = real time)
BOOL[2…15]: Not used
Reserved
Reserved
1 Get Basic
Information
STRUCT of:
WORD
STRUCT of:
BYTE
BYTE
STRUCT of:
LWORD
BOOL[16]
Fault code
Fault source
DSI port
DSI Device Object
Fault time stamp
Timer value (0 = Timer not supported)
BOOL[0]: (0 = invalid data, 1 = valid data)
BOOL[1]: (0 = elapsed time, 1 = real time)
BOOL[2…15]: Not used