Rockwell-automation 1769-SM2 Compact I/O DSI/Modbus Communication Modu Uživatelský manuál Strana 170

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 204
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 169
B-8 Module Parameters
47 [RTU Tx Delay 3]
Sets the CH3 inter-frame delay used to delay the
sending of a transmit packet when the module is in
Multi-Drive mode and Parameter 37 - [DSI I/O
Cfg 3] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 3.5
character times is used.
Default: 0 milliseconds
Minimum: 0 milliseconds
Maximum: 500 milliseconds
Type: Read/Write
Reset Required: Yes
48 [RTU MsgTimeout 3]
Sets the amount of time in seconds that the
module will wait for a response from a ModBus
RTU CH3 slave when the module is in Multi-Drive
mode and Parameter 37 - [DSI I/O Cfg 3] is set to
“5” (RTU Master).
Default: 2 seconds
Minimum: 0 seconds
Maximum: 60 seconds
Type: Read/Write
Reset Required: Yes
Parameter
No. Name and Description Details
Zobrazit stránku 169
1 2 ... 165 166 167 168 169 170 171 172 173 174 175 ... 203 204

Komentáře k této Příručce

Žádné komentáře