Publication 1761-UM006E-EN-P - August 2005
ENI/ENIW Configuration (Nodes 241 to 254) 4-13
These parameters are described in more detail in the following
sections.
Node 254 - Ethernet Hardware Address
You will find the hardware address on a label affixed to the ENI/ENIW
as shown to the left. The hardware address can also be read from
node address 254.
250 TCP/IP Configuration Integers 4, 8, 12, 16,
or 20
Valid IP Address 000.000.000.000
192.168.1.254
(5)
249 From String ASCII String 1 ENI/ENIW Identifier
(3)
248
Save/Reset
(4)
Integer 1 0 = save configuration to flash
1 = simple reset
2 = reset to out-of-box
defaults
3 = reset to out-of-box, except
maintain current IP
configuration
n/a
245 Configuration Security
Mask
(5)
Integers 4 Valid IP Address 000.000.000.000
244
SMTP Authentication
(5)
Integer 1 0 = Disabled
1 = Enabled
Disabled
243
SMTP Password
(5)
ASCII String 1 64 character password null
242
SMTP Username
(5)
ASCII String 1 64 character username null
241
Ethernet Speed/Duplex
(5)
Integer 1 0 = Auto Negotiate
1 = 10 Mbps half-duplex
2 = 10 Mbps full-duplex
3 = 100 Mbps half-duplex
4 = 100 Mbps full-duplex
10 Mbps half-duplex (series A, B)
Auto Negotiate (series C, D)
(1) Changes to the Baud Rate take effect when the ENI/ENIW power is cycled, or the configuration is saved to flash.
(2) Series C and higher.
(3) The ENI/ENIW address, 192.168.1.254 will be replaced by the IP address assigned to the ENI/ENIW. For example, the string may be ENI191.225.181.52@eni1761.org. If
the ENI/ENIW does not have an assigned IP address, the str
ing will be read as ENI192.168.1.254@eni1
761.org for the ser
ies D or
[email protected] for series A, B, or C.
(4) See page 4-19 for more information on Save/Reset.
(5) Series D only.
Table 4.1 Configuration Node Functions
Node Function Data Type Number of
Elements
Options Default
CAT FRN
1761-NET-ENI 2.20
SER
B
EXTERNAL POWER REQUIREMENTS
24 V dc +10/-15% AT 100 mA
N.E.C. CLASS 2
USE EXTERNAL DC SOURCE
FOR CLASS I DIVISION 2
APPLICATIONS. SEE
INSTALLATION INSTRUCTIONS
24VDC
CHS
GND
NEUT
DC
MADE IN U.S.A.
ETHERNET ADDRESS
CUS
R
LISTED IND.CONT.EQ. FOR HAZ.
LOC. A196
OPERATING TEMPERATURE CODE T3C
ETHERNET
INTERFACE
CLASS I, GROUPS A,B,C, AND D, DIV 2
N223
EN I*B22001020001 FAC . xx
FF-FF-FF-FF-FF-FF
Hardware
Address