Strany 1 - Backup Systems

Chapter 1PLC3 Programmable Controller Backup SystemsUser Manual

Strany 2 - Important User Information

Choosing a Backup ConfigurationChapter 11-3Primary processor - the processor that is controlling outputs. Whenswitchover to the backup processor occur

Strany 3 - Table of Contents

Programming TechniquesChapter 55-19When you select backup, you assign the same Data Highway or DataHighway Plus station number to both the scanner mod

Strany 4 - Table of Contentsii

Programming TechniquesChapter 55-20When you do not select backup, you assign a unique Data Highway (0008to 3768) or Data Highway Plus (008 to 778) sta

Strany 5 - What This Manual Contains

Programming TechniquesChapter 55-21Figure 5.7Sending a Message at Switchover| B1:0 S0:3 +MSG–––––––––––––––––––––––––+|

Strany 6 - Terms and Conventions

Programming TechniquesChapter 55-22another station on the Data Highway isinitiating a messagepossibly neither of the processors will respond to themes

Strany 7 - Related Publications

Programming TechniquesChapter 55-23for the primary and backup processors. Then, place executable instructionsabove the rung and disallowed instruction

Strany 8 - Backup Concepts

Chapter 66-1Diagnosing FaultsThis chapter describes how to diagnose faults in a PLC-3 backup systemusing: status indicators on the front panels of pr

Strany 9

Diagnosing FaultsChapter 66-2Now the backup processor is controlling outputs. If the backup processorattempts to execute the same logic rung that caus

Strany 10 - Chapter 1

Diagnosing FaultsChapter 66-3Figure 6.1Processor Front Panel10921PROCESSOROUTPUTSPROGRAMACCESSTable 6.AStatus Indicators for Primary Processor Indicat

Strany 11 - Choosing a Backup

Diagnosing FaultsChapter 66-4Table 6.BStatus Indicators for Backup Processor Indicator Status DescriptionPROCESSOR GREEN Backup processor is active (n

Strany 12

Diagnosing FaultsChapter 66-5Figure 6.2Indicator Locations for 1775S4 and 1775SR Scanner ModulesPASS and FAIL indicatorsThumbwheel switchI/O channel

Strany 13

Choosing a Backup ConfigurationChapter 11-4There are two backup configurations: scanner backup (Figure 1.2) which uses only I/O scanner modules MX bac

Strany 14 - Choosing a Switchover

Diagnosing FaultsChapter 66-6Figure 6.4Indicator Locations for 1775MX Memory Communication ModulePASS and FAIL indicatorsStatus indicators1775 - MXSc

Strany 15

Diagnosing FaultsChapter 66-7Table 6.EData Highway/Data Highway Plus Status Indicators for 1775S5, SR5Scanner ModulesIndicator Status DescriptionXMT

Strany 16 - Installing a Backup System

Diagnosing FaultsChapter 66-8Diagnosing Faults with Status Word BitsAnother method of diagnosing faults is to examine the contents of statuswords in t

Strany 17 - Chapter 2

Diagnosing FaultsChapter 66-9Creating the Fault RoutineThe fault routine requires two rungs; one rung as the first rung in themain ladder program me

Strany 18

Diagnosing FaultsChapter 66-10Figure 6.5Main Routine (RM0) Rung S0:3 + XOR –––––––––––––––+ + XOR –––––––––––––––+ + XOR ––––––

Strany 19

Diagnosing FaultsChapter 66-11|| +–––––––––––––––––––––+| 10988I

Strany 20

Diagnosing FaultsChapter 66-12Keep the following points in mind when you use the fault routine in yourladder program. the rung in the main routine m

Strany 21 - Shielding Considerations

Diagnosing FaultsChapter 66-13Figure 6.7Major Fault BitsStack faultDeactiveBackup cable faultBad addressBad instructionConfiguration faultMemory parit

Strany 22 - Configuring the I/O Chassis

Diagnosing FaultsChapter 66-14Table 6.J ResultsIf the Processor Detects: The 1775 - GA or 1775 - S4BProcedure Will Display:No fault NO FAULT DETECTEDA

Strany 23 - Configuring Scanner Modules

With offices in major cities worldwideWORLDHEADQUARTERSAllen-Bradley1201 South Second StreetMilwaukee, WI 53204 USATel: (414) 382-2000Telex: 43 11 016

Strany 24

Choosing a Backup ConfigurationChapter 11-5How MX Backup WorksFigure 1.3 shows the implementation of MX backup. The scanner modulesstill control I/O c

Strany 25

Choosing a Backup ConfigurationChapter 11-6Selecting Scanner or MX BackupTable 1.A and Table 1.B summarize the attributes of scanner backup andMX back

Strany 26

Choosing a Backup ConfigurationChapter 11-7The three methods of switching control of outputs from the primary to thebackup processor are: automatic s

Strany 27

Choosing a Backup ConfigurationChapter 11-8SwitchoverMethod:Attributes:ManualSwitchover When the primary processor faults, the system shuts down as t

Strany 28

Chapter 22-1Installing a Backup SystemThis chapter describes how to install PLC-3 and PLC-3/10 backupsystems. Specifically, it provides recommendation

Strany 29

Installing a Backup SystemChapter 22-2Important: The number one scanner module (thumbwheel set to 1) inboth primary and backup processors must be a 1

Strany 30 - Channel Wiring

Installing a Backup SystemChapter 22-3Figure 2.1Connections for a PLC3 Backup System Using Scanner BackupTo EarthGroundBlueShieldClearTo otherI/O Cha

Strany 31

Installing a Backup SystemChapter 22-4Figure 2.2Connections for a PLC3 Backup System Using MX BackupTo EarthGroundBlueShieldClearTo otherI/O Chassisi

Strany 32

Because of the variety of uses for this product and because of thedifferences between solid-state products and electromechanical products,those respon

Strany 33

Installing a Backup SystemChapter 22-5Figure 2.3Connections for a PLC3/10 Backup System Using Scanner BackupTo EarthGroundBlueShieldClearTo otherI/O

Strany 34

Installing a Backup SystemChapter 22-6For a PLC-3 backup system, it is important to choose suitable powersupplies and make sure they are connected pro

Strany 35

Installing a Backup SystemChapter 22-7You must configure all I/O chassis for backup mode operation. Each I/Ochassis has eight switches. Two of the swi

Strany 36

Installing a Backup SystemChapter 22-8Setting Switch 2The processor restart lockout switch (switch 2) must be ON so the backupprocessor is capable of

Strany 37

Installing a Backup SystemChapter 22-92. Set all backup switches on all other scanner modules, if any arepresent, in both the primary and backup proce

Strany 38

Installing a Backup SystemChapter 22-10Figure 2.7Location of Backup Switches for 1775S5 and 1775SR5 ScannerModules18754Backup Switch atBottom Edge o

Strany 39 - Communication Modules

Installing a Backup SystemChapter 22-11Selecting a Backup CableChoose a backup cable for the switchover method desired. Table 2.C liststhe choices. Se

Strany 40

Installing a Backup SystemChapter 22-12Figure 2.10Backup Cable Wiring for Scanner Backup with Automatic Switchoverwith Controllable Switchback (Cat. N

Strany 41 - Operating a Backup System

Installing a Backup SystemChapter 22-13Figure 2.11Backup Cable Wiring for Manual Switchover (Cat. No. 1775CBB)1324561324561775CBBBACKUP CABLESCANNER

Strany 42 - Chapter 3

Installing a Backup SystemChapter 22-14Figure 2.12Connections for Scanner BackupPrimary Processor Backup ProcessorBackupcable(seetext)10395Application

Strany 43

Preface P1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Manual Objectives P1. . . . . . . . . . . . . . . . . . .

Strany 44 - Figure 3.1

Installing a Backup SystemChapter 22-15There are four I/O serial communication channels per scanner. Dependingon your system architecture, you can use

Strany 45 - Procedure Selection

Installing a Backup SystemChapter 22-16Connecting I/O Communication ChannelsFigure 2.14 shows the connections when using I/O channel 1.Figure 2.14Conn

Strany 46

Installing a Backup SystemChapter 22-17If you designate another I/O channel for use as an I/O communicationchannel, replace the references to I/O chan

Strany 47

Installing a Backup SystemChapter 22-18Connecting an I/O Channel for PeertoPeer CommunicationAny I/O channel can be used for peer-to-peer communicat

Strany 48 - Memory Communication Module

Installing a Backup SystemChapter 22-19If you designate another I/O channel for use as a peer-to-peercommunication channel, replace the references to

Strany 49 - Table 4.A

Installing a Backup SystemChapter 22-208. If the last scanner is a 1775-S4A or 1775-SR scanner module, installa 1770-XT terminator to the I/O channel

Strany 50 - Using LIST Functions

Installing a Backup SystemChapter 22-21Connecting an I/O Channel for Backup CommunicationAny I/O channel can be used for backup communication. Figure

Strany 51

Installing a Backup SystemChapter 22-22If you designate another I/O channel for use as a backup communicationchannel, replace the references to I/O ch

Strany 52

Installing a Backup SystemChapter 22-23TerminatorsThe first and last physical device of each I/O channel requires a terminator.Use discrete terminator

Strany 53

Installing a Backup SystemChapter 22-24To implement MX backup you need two 1775-MX memorycommunication modules, one for the primary processor and ano

Strany 54

Table of ContentsiiProgramming Techniques 51. . . . . . . . . . . . . . . . . . . . . . . . . Chapter Objectives 51. . . . . . . . . . . . . . .

Strany 55

Installing a Backup SystemChapter 22-25To configure MX backup, do the following:1. Insert one memory communication module in the primary processorand

Strany 56

Chapter 33-1Operating a Backup SystemThis chapter describes how to operate a backup system. It recommendsprocedures for: starting up a backup system

Strany 57

Operating a Backup SystemChapter 33-2Startup Procedure Method 11. Turn off both the primary and backup processors, if they are notalready off.2. Turn

Strany 58

Operating a Backup SystemChapter 33-3Startup Procedure Method 21. Turn off both the primary and backup processors, if they are notalready off.2. Turn

Strany 59

Operating a Backup SystemChapter 33-4Figure 3.1Example Rung for Performing Memory Download at StartupDNMessageControlChannelDownload#B0:0E2.14.105ERB1

Strany 60

Operating a Backup SystemChapter 33-5To troubleshoot and/or repair a faulted processor, you may have todisconnect it.To disconnect a faulted processor

Strany 61

Operating a Backup SystemChapter 33-6Restart Procedure Method 11. Turn off both processors, if they are not already off.2. Reconnect the backup cable

Strany 62

Operating a Backup SystemChapter 33-7Restart Procedure Method 21. For the scanner backup configuration, place the switch, located in thebackup cable,

Strany 63

Chapter 44-1Using the 1775MXMemory Communication ModuleThis chapter describes how to use 1775-MX memory communicationmodules. Depending on your appli

Strany 64 - Using Message Instructions

Using the 1775MXMemory Communication ModuleChapter 44-2As shown in Table 4.A, you can control operation of memorycommunication modules by using: LIS

Strany 65

PrefaceP-1PrefaceThis manual shows you how to install, configure, and operate a backupsystem configured with PLC-3 or PLC-3/10 processors.In this man

Strany 66

Using the 1775MXMemory Communication ModuleChapter 44-3The following sections describe how to control memory communicationmodules by using LIST funct

Strany 67

Using the 1775MXMemory Communication ModuleChapter 44-4Figure 4.1LIST Menu for Primary and Backup ProcessorSYSTEM MODE1TEST MONITOR2*RUN MONITOR3PROG

Strany 68

Using the 1775MXMemory Communication ModuleChapter 44-5As shown in Table 4.B, a heading, which appears directly beneath thesystem identification, id

Strany 69

Using the 1775MXMemory Communication ModuleChapter 44-6The MCM OPERATION menu contains an entry for each LIST functionlisted in Table 4.D. These func

Strany 70

Using the 1775MXMemory Communication ModuleChapter 44-7Inactive CommandThe INACTIVE command lets you discontinue continuous data table andfile transf

Strany 71

Using the 1775MXMemory Communication ModuleChapter 44-8File Selection CommandTo specify a group of files, select the entry FILE SELECTION in theMCM O

Strany 72

Using the 1775MXMemory Communication ModuleChapter 44-9Important: Timers and counters cannot be separated into control, preset,and accumulated value

Strany 73

Using the 1775MXMemory Communication ModuleChapter 44-10Data Table Transfer CommandThe DATA TABLE XFER command lets you transfer all of the data tabl

Strany 74

Using the 1775MXMemory Communication ModuleChapter 44-11Memory Download CommandThe MEMORY DOWNLOAD command lets you transfer the entirecontents of th

Strany 75

Using the 1775MXMemory Communication ModuleChapter 44-12When you select the LOCK SYSTEM command, the memorycommunication module attempts to acquire t

Strany 76

PrefaceP-2Information that is especially important to note is identified by three labels: WARNING CAUTION ImportantWARNING: tells you of circumstances

Strany 77

Using the 1775MXMemory Communication ModuleChapter 44-13Enable Program Compare CommandThe ENABLE PROG COMP command lets you compare the ladderprogram

Strany 78

Using the 1775MXMemory Communication ModuleChapter 44-14Disable Program Compare CommandThe DISABLE PROG COMP command lets you disable the programcomp

Strany 79

Using the 1775MXMemory Communication ModuleChapter 44-15To enter the program compare limits, do the following:1. Select the command PROG COMP LIMITS

Strany 80 - Error Codes

Using the 1775MXMemory Communication ModuleChapter 44-16Backup to Primary Data Transfer CommandThe BACKUP TO PRIMARY DATA TRANSFER command lets youen

Strany 81

Using the 1775MXMemory Communication ModuleChapter 44-17Operation of a memory communication module using message (MSG)instructions follows the same c

Strany 82

Using the 1775MXMemory Communication ModuleChapter 44-18Command DescriptionAbbreviationENABLE COMPARE E C The memory communication modulecompares a s

Strany 83 - Switchover

Using the 1775MXMemory Communication ModuleChapter 44-19See Table 4.H when creating a message instruction:Table 4.HMessage Instruction ComponentsEnte

Strany 84 - Timing Considerations at

Using the 1775MXMemory Communication ModuleChapter 44-20Start $ <file list> CommandThe START $<file list> command lets you transfer selec

Strany 85

Using the 1775MXMemory Communication ModuleChapter 44-21Table 4.IData Table Section SpecifiersData Table Selection SpecifierOutput Image OInput Image

Strany 86

Using the 1775MXMemory Communication ModuleChapter 44-22Figure 4.3Example Rung Illustrating Continuous File Transfer| B1:0 S0:3

Strany 87 - Communication Overhead

PrefaceP-3For more information about components used with the PLC-3 backupsystem, see the publications listed in Table B.Table BRelated PublicationsPu

Strany 88

Using the 1775MXMemory Communication ModuleChapter 44-23Transfer $ <file list> CommandThe TRANSFER $<file list> command lets you transfer

Strany 89

Using the 1775MXMemory Communication ModuleChapter 44-24Start Data CommandThe START DATA command lets you transfer the entire contents of thedata tab

Strany 90 - Using Data Table Status Bits

Using the 1775MXMemory Communication ModuleChapter 44-25Transfer Data CommandThe TRANSFER DATA command lets you transfer all sections of the datatabl

Strany 91

Using the 1775MXMemory Communication ModuleChapter 44-26Important: A memory download will not occur if:- the backup processor has insufficient memor

Strany 92

Using the 1775MXMemory Communication ModuleChapter 44-27You can check the status of each processor by looking at file 4, word 0 ofthe status section.

Strany 93

Using the 1775MXMemory Communication ModuleChapter 44-28Table 4.JEnable CompareIf the memory communication module: Then:completes the program compare

Strany 94

Using the 1775MXMemory Communication ModuleChapter 44-29For example, if the primary processor encountered a message instructioncontaining the command

Strany 95

Using the 1775MXMemory Communication ModuleChapter 44-30Disable Outputs CommandThe DISABLE OUTPUTS command lets you inhibit the backup processorfrom

Strany 96

Using the 1775MXMemory Communication ModuleChapter 44-31List Control CommandThe LIST CONTROL command lets you redirect control of a memorycommunicati

Strany 97 - Data Highway Plus

Using the 1775MXMemory Communication ModuleChapter 44-32Status On CommandThe STATUS ON command lets you enable data transfer from the backupprocessor

Strany 98

Chapter 11-1Choosing a Backup ConfigurationThe information in this chapter can help you: understand backup concepts evaluate different backup config

Strany 99

Using the 1775MXMemory Communication ModuleChapter 44-33Table 4.K is a list of error codes. These error codes may appear while youare controlling the

Strany 100 - Chapter 5

Using the 1775MXMemory Communication ModuleChapter 44-34If an error occurs, check the following: If the backup processor is powered down or faulted

Strany 101

Chapter 55-1Programming TechniquesThis chapter describes techniques you can use to program a PLC-3 backupsystem. In this chapter we describe: input c

Strany 102

Programming TechniquesChapter 55-2Using Repetition to Handle Short Input PulsesOne method of handling short input pulses is to repeat the rungs that r

Strany 103 - Programming Considerations

Programming TechniquesChapter 55-3When using PLC-3 processors in a backup system configuration, programscans are not synchronized; and, although switc

Strany 104

Programming TechniquesChapter 55-4If the start pushbutton is pressed for too short a time, the input change maybe seen by the primary processor but no

Strany 105 - Diagnosing Faults

Programming TechniquesChapter 55-5The force table is not transferred from the primary to the backup processorover any communication channel. Thus, if

Strany 106 - Locating a Fault

Programming TechniquesChapter 55-6A PLC-3 backup system using memory communication modules requiresthe least amount of communication overhead. Data i

Strany 107

Programming TechniquesChapter 55-7Figure 5.3Programming for Block Transfer Inputs| Run/ BTR|| Backup Done|| S0:3 B200:12

Strany 108

Programming TechniquesChapter 55-8+––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––(MCR)–+||Other Program Rungs

Strany 109

Choosing a Backup ConfigurationChapter 11-2Why Use a Backup System?Backup is useful for applications in which an unexpected shutdown iscostly or other

Strany 110

Programming TechniquesChapter 55-9Another approach for reducing the amount of data transferred across abackup communication channel is to use Data Hig

Strany 111

Programming TechniquesChapter 55-10Backedup/Notbackedup BitThe backed-up/not-backed-up bit (file 0, word 3, bit 16) is set when optionswitch 2 on t

Strany 112 - A Logic Diagnostic Routine

Programming TechniquesChapter 55-11The checksum is stored in file 0, word 5 and the checksum done bit isstored in file 0, word 4, bit 17 of the data t

Strany 113

Programming TechniquesChapter 55-12Refer to the PLC-3 Family Programmable Controller ProgrammingReference Manual (publication 1775-6.4.1) for detailed

Strany 114

Programming TechniquesChapter 55-131775MX Module CommunicationIf the PLC-3 backup system uses memory communication modules, thereare additional bits

Strany 115

Programming TechniquesChapter 55-14Important: Upon completing the program compare function, the memorycommunication module sets either bit 12 or 13 i

Strany 116

Programming TechniquesChapter 55-15Figure 5.6Program Compare Status Information for the Memory CommunicationModuleUnused value (always 0)User program

Strany 117

Programming TechniquesChapter 55-161775MX Module BackuptoPrimary Transfer Data WordsIn response to the BACKUP TO PRIMARY DATA TRANSFER in LISTor th

Strany 118

Programming TechniquesChapter 55-17Series A, Revision D (or later) 1775KA ModulesWhen using series A, revision D (or later) communication adaptermodu

Strany 119

Programming TechniquesChapter 55-18As long as the primary processor is controlling outputs, the stationaddress of the communication adapter module in