9-6 Troubleshooting
Error Codes Generated by
the ENI/ENIW
This table shows the MSG error codes that may be generated by the
ENI/ENIW to the connected DF1 device.
Table 9.7 ENI/ENIW-Generated Error Codes
Error Code Description of Error Condition
10H Target node cannot respond because of incorrect command parameters or unsupported command. Possible causes:
The data size of the message is invalid.
The data format is incorrect for any of the supported PCCC messages.
Register parameters are not formatted correctly, or there is not enough data provided.
RS-232 configuration packet data is not the correct size.
The Node Address is invalid or out-of-range.
The distant ENI/ENIW, controller, or device may not be responding.
There may be a break in the connection between the ENI/ENIW devices or controllers.
BOOTP/DF1 parameter is invalid.
30H Target node responded with: Remote station host is not there, disconnected, or shutdown.
D0H One of the following:
No IP address configured for the network or ENI/ENIW not configured for Node Address used.
Bad command - unsolicited message error.
Bad address - unsolicited message error.
No privilege - unsolicited message error.