8-20 Connecting CompactLogix Controllers on Ethernet
3. Click “OK” to accept the default driver name.
At that point the station mapping screen will appear as
illustrated here. Double click on the row below “Host Name”,
and enter the TCP/IP addresses that match the devices on your
network that you will need access to.
When you are done entering the stations, click OK to close the
station mapping window.
4. Open the Who Active screen by clicking on the Communications
pull-down menu and selecting Who Active.
If your system is properly connected, you should be able to
click on the + sign left of the AB_ETH-1 driver you created to
establish Ethernet communications with the ENI/ENIW series B,