THEORY OF OPERATION
In
accordance
with
TMR
practice,
channel
output
command
information
from
the
system
follows
three
identical
paths
through
the
Digital
Output
Module
(Figure
2
-
4)
each
path
at
the
command
of
its
own
m
icrocontroller
in
the
Common
Interface.
As
the
switching
speed
of
the
module
exceeds
the
system
scan
rate
the
channel
data
can
be
converted
to
serial
form
before
entering
the
module
from
the
Common
Interface.
In
this
manner
32
output
channels
can
be
served
by
just
three
paths
instead
of
96.
The
three
data
streams
are
each
applied
to
opto
-
isolators
which
mark
the
interface
between
the
system
and
output
sides
of
the
circuit
and
provide
a system
to
field
channel
isolation
of
1000V
minimum.
The
data
streams
are
then
applied
to
the
32
-
bit
output
shift
registers.
The
serial
bits
are
clocked
successively
into
the
shift
registers
until
the
32nd
bit
has
been
received,
the
registers
then
latch
the
data
and
present
it
on
the
32
-
bit
buses
(CHANA,
CHANB
and
CHANC)
to
t
he
output
switches.
The
data
is
refreshed
in
this
manner
at
each
scan
of
the
system.