Triguard
SC300E
The
module
uses
hardware
circuitry
and
configuration
lin
ks
that
enable
the
system
to
identify
the
module
type
and
configuration
mode.
The
configuration
links
1,
2 and
3 are
located
in
the
top
right
-
hand
corner
of
the
module
(see
Figure
1.1).
Link
1 allows
the
module
to
be
set
up
for
321
or
320
mode
operation.
320
mode
means
that
the
system
will
continue
to
function
with
two
out
of
three
serviceable
circuits.
In
321
mode
the
system
will
continue
to
function
with
one
out
of
three
serviceable
circuits.
No
link;
defaults
to
320
mode.
Link
2 (HLV/GTZ)
determines
whether,
in
the
event
of
a failure
due
to
321/320
action,
the
last
read
values
are
held
(HLV)
or
are
set
to
zero
(GTZ).
No
link;
defaults
to
GTZ
mode.
Link
3 is
factory
set
to
HW
and
if
changed
to
ICCB
(see
Note)
or
removed
the
module
defaults
to GTZ.
(NOT
E:
ICCB
is
a silk
screen
identifier
used
on
output
modules
only)
Table
2
-
1.
Link
settings
versus
operation
Link
settings
(see
Notes)
Processor
and
interface
status
Link
1
Link
2
Link
3
3 MPPs
& associated
path
CI
operating
2 MPPs
& associated
path
CI
operating
1 MPP
& associated
path
CI
operating
321
X X
Normal Normal Normal
320
HLV
HW
Normal Normal
HLV
320
HLV
ICCB
Normal Normal
GTZ
320
GTZ
X
Normal Normal
GTZ
320
Missing
X
Normal Normal
GTZ
Notes:
X = Don’t
care
or
missing
link
Link
1 missing
=
320
operation
HL
= Last
valid
output
held
(Output
maintained)
GTZ
= Go
To
Zero
(Output
turned
off)