Addressing syntax for Allen–Bradley programmable controllers D–11
PLC–5 (Enhanced) timer, counter, control,
SFC status, message, PID, block transfer, and
token data files
FFnnn:eee.MNE[ss]/bb
FF File type:
T = Timer
C = Counter
R = Control
SC = SFC status
MG = Message
PD = PID control
BT = Block transfer
TD = Token data
nnn File number: 3 – 999 decimal
For direct driver communication, timer, counter,
and control file types use the default file number
if the file number is absent. The default numbers
are 4 (timer), 5 (counter), and 6 (control).
eee Element number: 0 – 999 decimal
MNE Member mnemonic (see mnemonic tables
starting on page D-30)
ss Submember
Only applies to .ADDR and .DATA members of
PID structure and .DATA member of
MSG structure.
bb
(optional) Bit number: 0 – 15 decimal
Only applies to analog word members.
Example: MG59:33.DATA[0]/15