16–10 RSView32 User’s Guide
TransType The type of alarm that was generated. The types are:
InAlmIn Alarm (severities 1 through 8)
OutAlmOut of Alarm
AckedAcknowledged
RmAckRemote Acknowledged
InFltIn Fault
OutFltOut of Fault
SupOnSuppress On
SupOfSuppress Off
TagName The name of the tag or alarm event that caused the
alarm.
TagValue The value of the tag at the time the alarm occurred.
TagType The type of tag in alarm: A for analog, D for digital, S for
string.
ThreshVal The threshold value.
ThreshNum The threshold number.
ThreshLabl The threshold label.
Severity The alarm severity (1 is highest severity and 8 is lowest
severity).
DstFlag The Daylight Savings Time (DST) flag, where Y means
DST is in effect and N means DST is not in effect. This
number is for RSView32 internal use only.
UserId The user that was logged on when the alarm occurred.
AlarmType The number RSView32 assigns to the transaction type.
Dscription The message that is associated with the transaction
(alarm) type.
This column Contains