18Ć18 AutoMax Programming Executive Version 3.x
18.3.1 Monitor Analog Display
The following fields will be displayed on the Monitor Analog screen
for each variable:
(#) Ć
Identifies the D/A channel (0 or 1) through which
the value will be displayed.
Task Ć Identifies the task in which the variable is defined.
This field is blank if the variable is common.
Variable Ć Variable name, including the type character %"
for single precision integers.
Scale Ć Identifies a scale factor of *16, *8, *4, *2, *1, *1/2,
*1/4, *1/8, or *1/16.
18.3.2 Outputting a Variable
The procedure for adding a variable is the same whether you are
actually adding the variable, or replacing a variable with another
variable.
Follow the procedure below to output a variable.
1. From the Monitor menu, select A" for analog.
2. Enter the slot number of the Processor on which the CML task is
running.
3. Select A" for Add to add a variable.
4. Enter the D/A converter through which the signal is obtained
(0
or 1). The converter corresponds to the display position. If you
enter a display position currently on the screen, the variable
associated with it will be replaced by the new variable you enter
in step 5 below.
5. If
the variable in question is a local variable,
enter the name of the
task in which the variable is defined. If the variable is a common
variable, i.e., configured for the rack using the Variable
Configurator, press the Enter" key or <CR> to skip over the
Task" field.
6. Enter the name of the variable in the Variable" field. Include the
type character %" for single precision integers. Type Enter" or
<CR>.
7. When the cursor has moved to the Scale" field, use the up and
down arrow keys to scroll through the available scale factors
described in 18.3.1 above. The default scale factor is 1.
8. Press Enter" or <CR> to terminate the entry and add it to the
display.