13Ć3On Line Menu: Info/Log
The Software ID" depends on the software (operating system) and
hardware
version of the UDC module. T
ick
Rate" refers to the speed
of the realĆtime clock in the UDC module. The Parameter File
Date/Time" will display the most recent date and time that the
parameter object file was generated. UDC Utilization" shows the
percentage of the UDC CPU's resources being used to run UDC
tasks. The UDC Utilization percentage is measured over a two
second
time window
. This value should be kept under 75% to ensure
that there are no overlaps in UDC task execution. Memory statistics
displayed for the UDC module are given in bytes.
The PMI OS Status" fields show whether the PMI operating system
has been loaded to each of the PMI Processors (Not Loaded or the
OS
type (e.g.,
SA3000) ). If the PMI Processor is not connected to the
UDC module, this field will display Not Connected". The PMI
Parameters" fields show whether the drive parameters have been
loaded to each of the PMI Processors (Installed or Not Installed). If
the PMI OS Status field is displaying Not Connected", the PMI
Parameters fields will be blank. If the PMI Processor is connected to
the UDC module, the modules contained in the PMI rack(s) will be
listed.
 
If you select a task using the Enter or <CR> before selecting
Info/Log,
AutoMax will display the task status and
the error log, if any
,
for the AutoMax or UDC task. A sample display is shown in figure
13.3.
ON LINE direct AUTOMAX C: \LIB\SYS\RACK
Info/Log
SLOT NAME TYPE PRI STATUS
5 APP1B Blk B Stop
NUMBER STATEMENT DATE TIME ERROR SPECIFIC
EscăExit
F1ăHelp
ERROR LOG
SOURCE DATE
08Ć31Ć1993
02:08:18p
49ă = ă31 HEX 0 No date 00:00 0 = 0 HEX
774 = 306 HEX 0 No date 00:00 0 = 0 HEX
Precision lost in integer control variable to real conversion
775 = 307 HEX 0 No date 00:00 0 = 0 HEX
Real to integer overflow in FOR statement TO value
Error 31: Slot=0 Bit=0 (Reg based on type of card in slot)
Net: drop=0,ą reg=0 Remote I/O:drop=0, slot=0, reg=0
Modbus: reg=n/a AutoMate: reg=n/a AĆB: file= n/a, reg=n/a Local I/O: reg=0
Figure 13.3 Ć Info/Log T
ask Information Display