EĆ3
Corrective action: correct the problem in application software. Error code 47 can
be caused by performing a PUT on a closed port. Error code 4A can be caused
by attempting to use Ethernet functions with the standard operating system
loaded. To use Ethernet functions, you must load the Ethernet operating system.
Multibus and Processor Bus STOP ALL Error Codes
50 Onboard parity error
51Ć54 Onboard bus error or access violation
55 Multibus parity error during read access
56Ć58 Multibus access violation or bus error
60 Network interrupt allocation failed
61 Network receiving queue overflow
62 Network transmit queue underflow
Corrective action: reset by cycling power and reĆloading configuration and
application tasks. If the small green LED labeled OK" on the Processor module
faceplate is off, replace the Processor module. Correct any incorrect accesses in
application software. Systematically swap out hardware modules. For error codes
55Ć58, if none of the above correct the problem, try replacing the backplane.
DriveĆRelated Error Codes
The following error codes indicate a power circuit or external drive system fault.
After correcting the problem, reset the Processor module to clear the error code.
80 Instantaneous overcurrent fault
Ć armature current exceeded IOC_THRESH value in CML task
81 Line sync loss fault
82 Tach loss fault
Ć 40% armature voltage with less than 5% tach feedback
83 Overspeed/overvoltage fault
Ć CML task OSV_FDBK exceeded OSV_THRESH number
84 Hardware overspeed fault
Ć drive analog module potentiometer setting exceeded
by input voltage
85 External IET fault
Ć external fault input triggered
86 Phase rotation fault
Ć incorrect phasing
87 Shorted SCR detected in power module
Corrective action: troubleshoot power circuit and external drive system.
Configuration Error Codes
The following error codes usually indicate a discrepancy between the actual
hardware configuration and the I/O definitions in the configuration for the rack.
E0 TASK specified in configuration uninstalled,
at wrong priority, of wrong type, on wrong
Processor module; wrong spelling of TASK
E1 Invalid configuration, configuration not successfully downloaded.
E2 I/O referenced in configuration is missing.
E3 I/O referenced in configuration is missing. Invalid configuration,
configuration not successfully downloaded.
E4 Error building task, insufficient memory in Processor Module.
Invalid configuration, configuration not successfully dovvnloaded.